Description
The KBS (КБС) bactericidal duct section is designed to disinfect air with ultraviolet radiation in the rectangular ducts of ventilation and air-conditioning systems of medical, children's, sports and other premises. Each size is made in four variants by total bactericidal flux; casing length per drawing is 1,130 mm. Designation example КБС 50-30: 50-30 is the flange connection size in cm. The catalogue gives a table of room categories with the required volumetric bactericidal dose, from 105 J/m³ (smoking rooms, public toilets, stairwells of medical facilities) to 385 J/m³ (operating and pre-operating rooms, delivery rooms, sterile zones, maternity-ward children's rooms). According to the manufacturer's catalogue: 9 sizes (from КБС 40-20 to КБС 100-50) with airflows from 1,700 to 10,800 m³/h; total bactericidal flux from 32 to 397 W, total power consumption from 0.15 to 1.875 kW, weight from 21.3 to 127.3 kg. Price on request — send a request and the supplier will reply with the price, lead time and delivery terms.
Specifications
- Type
- Duct section for ultraviolet air disinfection
- Application
- Air disinfection in ventilation of medical, children's, sports and other premises
- Model sizes
- 9 sizes: КБС 40-20 … КБС 100-50, 4 variants each
- Airflow
- 1,700–10,800 m³/h
- Total bactericidal flux
- 32–397 W
- Motor power
- 0.15–1.875 kW (total consumption)
- Connection size
- Flange A×B from 400×200 to 1000×500 mm
- Dimensions
- Length 1,130 mm (per drawing)
- Weight
- 21.3–127.3 kg
- Volumetric bactericidal dose by room category
- 105–385 J/m³
- Manufacturer
- JIHOZVENT, Tashkent (Uzbekistan)